In this guide
1. Record room-by-room extract rates
| Room | Airflow |
|---|---|
| Kitchen with electric cooker | 60 m³/h |
| Kitchen with gas cooker | 100 m³/h |
| Bathroom, shower room or combined bathroom | 50 m³/h |
| Separate toilet or laundry room | 25 m³/h |
| Store or dressing room | 0.2 air changes per hour |
2. Calculate supply air
The source uses 30 m³/h per person as an example from SP 60.13330.2020, subject to the floor-area conditions in the standard. Three people give 90 m³/h and four give 120 m³/h in that example.
3. Add the extract flows
In the example of a flat with an electric cooker, a bathroom and a separate toilet, 60 + 50 + 25 gives 135 m³/h. Compare the resulting figure with the calculated supply and balance the system around the design airflow.
4. Estimate clear duct area
Use A = Q / (3,600 × v), where A is in square metres, Q is airflow in m³/h and v is air speed in m/s. For 60 m³/h at 1 m/s, the result is about 0.0167 m², or 167 cm².
Cross-section examples
| Duct size | Clear area | At 0.6 m/s | At 1.0 m/s |
|---|---|---|---|
| 120 × 170 mm | 204 cm² | 44 m³/h | 73 m³/h |
| 140 × 140 mm | 196 cm² | 42 m³/h | 71 m³/h |
| 120 × 250 mm | 300 cm² | 65 m³/h | 108 m³/h |
| 140 × 270 mm | 378 cm² | 82 m³/h | 136 m³/h |
| 250 × 300 mm | 750 cm² | 162 m³/h | 270 m³/h |
5. Check shaft height and pressure losses
A cross-section calculation alone does not establish actual draught. Height, bends, transitions, grilles and the available supply air all matter. Check actual resistance and commissioning airflow against the ventilation design.
Worked example for a 150 m² house
With four occupants, supply is 120 m³/h in the example. The kitchen, bathroom and separate toilet add up to 135 m³/h of extract. The gas boiler room is handled separately under its own design requirements.
Frequently asked questions
Can I size a duct from air changes alone?
The worked method uses occupancy for supply to habitable rooms and the specified room rates for extract. The standard also gives air changes for some service rooms.
Will a 120 × 170 mm duct carry 100 m³/h?
At 1 m/s its theoretical flow is about 73 m³/h. Check a larger section or a different channel configuration against the design.
Why allow spare blocks?
The source allows 5–10% for cutting, damage during handling and unforeseen sections. Check your quantities against the actual shaft schedule.
What should I check when there is little draught?
Check the supply openings, transfer paths, extract grilles and duct cleanliness. If those are clear, review the shaft geometry and available pressure with the designer.