How to calculate residential ventilation

A worked method for estimating supply air, extract air and the cross-section of a ventilation duct.

In this guide

1. Record room-by-room extract rates

Extract airflows cited in SP 54.13330.2022
RoomAirflow
Kitchen with electric cooker60 m³/h
Kitchen with gas cooker100 m³/h
Bathroom, shower room or combined bathroom50 m³/h
Separate toilet or laundry room25 m³/h
Store or dressing room0.2 air changes per hour

2. Calculate supply air

The source uses 30 m³/h per person as an example from SP 60.13330.2020, subject to the floor-area conditions in the standard. Three people give 90 m³/h and four give 120 m³/h in that example.

3. Add the extract flows

In the example of a flat with an electric cooker, a bathroom and a separate toilet, 60 + 50 + 25 gives 135 m³/h. Compare the resulting figure with the calculated supply and balance the system around the design airflow.

4. Estimate clear duct area

Use A = Q / (3,600 × v), where A is in square metres, Q is airflow in m³/h and v is air speed in m/s. For 60 m³/h at 1 m/s, the result is about 0.0167 m², or 167 cm².

Cross-section examples

Theoretical flow by clear duct size
Duct sizeClear areaAt 0.6 m/sAt 1.0 m/s
120 × 170 mm204 cm²44 m³/h73 m³/h
140 × 140 mm196 cm²42 m³/h71 m³/h
120 × 250 mm300 cm²65 m³/h108 m³/h
140 × 270 mm378 cm²82 m³/h136 m³/h
250 × 300 mm750 cm²162 m³/h270 m³/h

5. Check shaft height and pressure losses

A cross-section calculation alone does not establish actual draught. Height, bends, transitions, grilles and the available supply air all matter. Check actual resistance and commissioning airflow against the ventilation design.

Worked example for a 150 m² house

With four occupants, supply is 120 m³/h in the example. The kitchen, bathroom and separate toilet add up to 135 m³/h of extract. The gas boiler room is handled separately under its own design requirements.

Frequently asked questions

Can I size a duct from air changes alone?

The worked method uses occupancy for supply to habitable rooms and the specified room rates for extract. The standard also gives air changes for some service rooms.

Will a 120 × 170 mm duct carry 100 m³/h?

At 1 m/s its theoretical flow is about 73 m³/h. Check a larger section or a different channel configuration against the design.

Why allow spare blocks?

The source allows 5–10% for cutting, damage during handling and unforeseen sections. Check your quantities against the actual shaft schedule.

What should I check when there is little draught?

Check the supply openings, transfer paths, extract grilles and duct cleanliness. If those are clear, review the shaft geometry and available pressure with the designer.